Home » Products » ICST Series – Commercial Slope-Top Covector

ICST Series – Commercial Slope-Top Covector

IDEAL SPACES| (STANDARD) Offices; Corridors; Lobbies; Maintenance Rooms; Stairwells; Other Similar Spaces (NEMA 4x) Food Processing Areas; Dairies; Breweries; Locker Rooms; Stadium Dugouts; Other Areas Subject To High Pressure Hosing and/or Wet Conditions

COLORS | White, Beige, Aluminum, Bronze, Black, Charcoal Gray & Stainless Steel

DIMENSIONS | See specifications

  • NEMA 4X model consists of stainless steel design rated for washdown and corrosive environments
  • Designed to mount on wall at sill height (or lower) and can be positioned directly on floor. End of unit can be positioned against adjacent sidewall if desired
  • Front cover fabricated from 16-gauge steel; back cover is constructed of 18-gauge steel
  • Thermal limit switch with linear type (full length) sensing bulb provides constant protection against overheating from any cause. Switch will automatically reset when normal operating temperatures are restored
  • Elements are long-life metal sheath type, anchored to allow for quiet expansion and contraction
  • Baked enamel finishes that are compatible with all interior decors
  • Attractive 45 sloped top discourages use of heater as a shelf or a stepstool
  • Units can be mounted from wall-to-wall or as discrete units in standard lengths of 28 in. to 10 ft.
  • Optional built-in controls include: thermostat; disconnect switch; transformer relay; and power relay (see specifications)
  • Accessories include complete line of matching splice sections, inside and outside corners, and blank sections
  • Pre-wired and designed for either right- or left-hand entry with connection of supply wiring from bottom, rear or end, as well multiple wiring of adjacent heaters from one entry point
  • All internal parts are accessible by removing cover for easy service access

Additional information

CATALOG NUMBER LENGTH NOMINAL WATTS TOTAL HEAT CAPACITY WATTS btu 120V 208V 240V 277V 347V 600V SHIP WT.
125 250 853 2.1 1.2 1 0.9
ICST02 28 188 375 1280 3.1 1.8 1.6 1.4 12 lbs.
250 500 1706 4.2 2.4 2.1 1.8 1.4
125 375 1280 3.1 1.8 1.6 1.4 1.1
ICST03 36 188 546 1925 4.7 2.7 2.4 2 1.6 15 lbs.
250 750 2560 6.2 3.6 3.1 2.7 2.2
125 500 1706 4.2 2.4 2.1 1.8 1.4
ICST04 48 188 750 2560 6.2 3.6 3.1 2.7 2.2 1.3 19 lbs.
250 1000 3412 8.3 4.8 4.2 3.6 2.9 1.7
125 625 2133 5.2 3 2.6 2.3 1.8 1
ICST05 60 188 940 3208 7.8 4.5 3.9 3.4 2.7 1.6 24 lbs.
250 1250 4266 10.4 6 5.3 4.5 3.6 2.1
125 750 2560 6.2 3.6 3.1 2.7 2.1 1.3
ICST06 72 188 1125 3840 9.4 5.4 4.7 4.1 3.2 1.9 26 lbs.
250 1500 5120 12.5 7.2 6.3 5.4 4.3 2.5
125 1000 3412 4.8 4.2 3.6 2.9 1.7
ICST08 96 188 1500 5120 7.2 6.3 5.4 4.3 2.5 37 lbs.
250 2000 6824 9.6 8.3 7.2 5.8 3.3
125 1250 4266 6 5.2 4.5 3.6 2.1
ICST10 120 188 1875 6400 9 7.8 6.8 5.4 3.1 45 lbs.
250 2500 8532 12 10.4 9 7.2 4.2
SUFFIX ADDITION TO HEATER CAT. NO. DESCRIPTION Notes
* T 1-Pole Thermostat Rated 24 amps @ 120-240 VAC and 22 amps @ 277 VAC. Pilot duty rating of 125 VA (all voltages). 60-120F temperature range; adjustable through outlet grille-tamper-resistant. Not available on three-phase heaters.
* 2T 2-Pole Thermostat Rated 24 amps @ 120-240 VAC and 22 amps @ 277 VAC. Pilot duty rating of 125 VA (all voltages). 60-120F temperature range; adjustable through outlet grille-tamper-resistant. (See Note 2 for amperage restrictions.)
* DS Disconnect Switch Double-pole, rated 20 amp @ 120-277 VAC. Two required for 3 heaters and 1 heaters over 20 amps
* TR Transformer Relay Single-pole, low voltage relay with built-in transformer (24 VAC control), rated 25 amps @ 120-240 VAC and 22 amps @ 277 VAC. 17 amps @ 347V , 12 amps @ 600V (See Note 6). Not available on 3 heaters.
* PR Power Relay Single-pole magnetic relay, rated 18 amps @ 120-600 VAC. (See Notes 1, 3 and 6.) Specify control voltage.Rated 24 amps @ 120-240 VAC and 22 amps @ 277 VAC. Pilot duty rating of 125 VA (all voltages).
ICSTIC 2 Inside corner (requires additional wall space – use with ST model only).
ICSTOC 2 Outside corner (requires additional wall space – use with ST model only).
ICSTJS 1 Splice plate wide, coverage gap up to 1/2 (use with ST model only).
STO2BS 2-foot Blank Section (unheated section)
STO4BS 4-foot Blank Section (unheated section)
STO6BS 6-foot Blank Section (unheated section)
STO8BS 8-foot Blank Section (unheated section)

This product is a custom Made-To-Order (MTO) product. It is not covered by the Marley Engineered Products Merchandise Return Policy and is non-cancellable, exchangeable, or returnable.